Entered Date:

09/27/2010

Applicant:

BP 250 RCM INVESTORS LLC 23.8% & THACKERA

Description:

Full Inspection conducted 09/27/10 I have received a copy of this report and understand the corrections needed: ______________ Business Rep.: Willie Adams Phone: 584-1605 Inspector: _________________, David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after) Certificate of Occupancy: ON FILE & POSTED Sprinkler system tagged 9/10/10 by Kazal Provide and retain copies of system inspection reports.

Outstanding Inspections

Case Number: T10FR01974
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
09/27/2010 INSP - FULL dgreenl1 Violation Correct deficiencies noted in Kazal hood system deficiency report dated 5/6/10 TO10FR01356 _____ Clean or replace heads above charbroiler _____ Replace caps for heads above charbroiler also: _____ Clean accumulation of grease under fryers TFC 315.2.4 - Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction _____ Remove storage above ceiling in AC mechanical area TFC 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles: _____ Kitchen above stand up reach in cooler _____ Kitchen above uniform storage _____ Hallway to bar, under AC unit _____ AC access room ladder TFC 703.1.1 - Fireblocking and draftstopping. Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction. _____ Repair drywall in above ceiling AC access area TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. ***Repair Emergency Lights: _____ Hall to bar _____Hall to DR _____ DR North wall, _____ DR South wall _____ Bar North wall, _____ Bar South wall 3003.5.3 - Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling…. _____ Secure all cylinders

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01974
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/30/2010 INSP - REINSPECTION JLOYA Approved Fire code violations abated.