Case: T10FR01974

Parcel: 12810079B

Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T10FR01974

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
09/27/2010 INSP - FULL Violation Correct deficiencies noted in Kazal hood system deficiency report dated 5/6/10 TO10FR01356

_____ Clean or replace heads above charbroiler

_____ Replace caps for heads above charbroiler
also:
_____ Clean accumulation of grease under fryers

TFC 315.2.4 - Attic, under-floor and concealed spaces.
Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction

_____ Remove storage above ceiling in AC mechanical area

TFC 703.1 - Maintenance
The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.
***Replace missing ceiling tiles:
_____ Kitchen above stand up reach in cooler
_____ Kitchen above uniform storage
_____ Hallway to bar, under AC unit
_____ AC access room ladder

TFC 703.1.1 - Fireblocking and draftstopping.
Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction.

_____ Repair drywall in above ceiling AC access area

TFC 107.1 - Maintenance of safeguards.
Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.
***Repair Emergency Lights:
_____ Hall to bar _____Hall to DR
_____ DR North wall, _____ DR South wall
_____ Bar North wall, _____ Bar South wall

3003.5.3 - Securing compressed gas containers, cylinders and tanks.
Compressed gas containers, cylinders and tanks shall be secured to prevent falling….

_____ Secure all cylinders