Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/23/2010

Applicant:

BEST OF EVERYTHING INC

Description:

Full Fire Prevention Inspection. Donna DiFiore------884-9289

Outstanding Inspections

Case Number: T10FR01790
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag all portable fire extinguishers.
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Remove all grease accumulation from the kitchen hood system and provide documentation of the cleaning. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____1. Service and test the kitchen hood extinguishing system and provide a copy of the inspection report for fire department records.
08/23/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1011.5.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. _____1. The east exit sign shall be internally or externally illuminated at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01790
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/20/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.