Case: T10FR01790

Parcel: 117042860


Addresses:

533 N 4TH AV


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01790

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

_____1. Service and test the kitchen hood extinguishing system and provide a copy of the inspection report for fire department records.
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____1. Service and tag all portable fire extinguishers.
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

_____1. Remove all grease accumulation from the kitchen hood system and provide documentation of the cleaning.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____