Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/17/2010

Applicant:

135CONGRESS LLC

Description:

Full Fire Prevention Inspection Amanda Nobrega-----624-9800

Outstanding Inspections

Case Number: T10FR01749
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/17/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. The automatic sprinkler system for the basement shall be inspected and tested, any deficiencies noted shall be corrected. NOTE: Provide a copy of the sprinkler system inspection report for fire department records.
08/17/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____1. Service the kitchen hood extinguishing system.
08/17/2010 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure all compressed gas cylinders with a chain or strap to prevent falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01749
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/08/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.