Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR01749
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____1. Service the kitchen hood extinguishing system. |
|
08/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. The automatic sprinkler system for the basement shall be inspected and tested, any deficiencies noted shall be corrected. NOTE: Provide a copy of the sprinkler system inspection report for fire department records. |