Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR01635
Case Details
Entered Date:
08/06/2010
Applicant:
VH PROPERTY LLC
Description:
Octopus car wash complaint.
Outstanding Inspections
Case Number: T10FR01635
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
08/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. ___Provide caps for FDC ___Lock sprinkler riser valve on open position. |
08/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report. |
08/06/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
08/06/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01635
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
08/17/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |