Case: T10FR01263
Case Details
Entered Date:
06/25/2010
Applicant:
ROSE DELA DMA FLP
Description:
La bodege fire inspection.
Outstanding Inspections
Case Number: T10FR01263
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. |
06/25/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger. |
06/25/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01263
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
07/09/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |