Alejandro's tortillas fire inspection.
Outstanding Inspections
Case Number: T10FR01262
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2010 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
06/25/2010 | VIOL - EMERGENCY PLAN/PREPARE | JLOYA | Violation | 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. |
06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. __ Cover empty slots at breaker panels. |
06/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. __ Provide coverage for all cooking appliances under hoods. |
06/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. |
06/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. |
06/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
06/25/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
06/25/2010 | VIOL - COMPRESSED GASES | JLOYA | Violation | Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel. *** Secure gas cylinder in an approved manner to avoid accidental dislodgment. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01262
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |