Case: T10FR01067
Case Details
Entered Date:
06/02/2010
Applicant:
LPR PROPERTIES LLC
Description:
Full Fire Prevention Inspection. Hal Elzweig 690-7385
Outstanding Inspections
Case Number: T10FR01067
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the cube adapter located in Hal's office NOTE: Replace it with a fused adapter. |
| 06/02/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the orange extension cord used to power the refridgerator loacted in the lab. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 06/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag all portable fire extinguishers. _____2. Replace the old battery in the smoke detector located in the hall by the front desk. |
| 06/02/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located in the Northeast back room. _____2. Repair or replace the emergency lighting unit located by the employee break room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01067
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |