Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/27/2010

Applicant:

RUDOLPH 1999 FAMILY TR

Description:

Dollar general fire inspection

Outstanding Inspections

Case Number: T10FR01057
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
05/27/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
05/27/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background
05/27/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01057
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/27/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
06/16/2010 INSP - REINSPECTION JLOYA Approved All violations abated.