Case: T10FR00942
Case Details
Entered Date:
05/12/2010
Applicant:
CIRCLE PLAZA ASSOCIATES LLC 50% &
Description:
Full Inspection
Outstanding Inspections
Case Number: T10FR00942
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2010 | INSP - FULL | jdavis | Correction Required | 1. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied -Repair or replace teh emergency backup lighting in the "Restroom Lobby" area 2. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated: -Women's fitting room -Custodial closet 3. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). - Repair panic hardware ni the "Bathroom Lobby" |