Case: T10FR00942

Parcel: 13419042D


Addresses:

7250 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T10FR00942

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/12/2010 INSP - FULL Correction Required 1. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
-Repair or replace teh emergency backup lighting in the "Restroom Lobby" area

2. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated:
-Women's fitting room
-Custodial closet

3. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. The maximum unlatching force shall not exceed 15 pounds (67 N).
- Repair panic hardware ni the "Bathroom Lobby"