Case: T10FR00783
Case Details
Entered Date:
04/21/2010
Applicant:
SETH FAMILY LIMITED PARTNERSHIP
Description:
Full Fire Prevention Inspection. Anna Garcia 623-5800
Outstanding Inspections
Case Number: T10FR00783
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag all portable fire extinguishers. Was not able to enter the office to finish the inspection. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 04/21/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double-keyed lock from the North exterior door. _____2. Remove the locking bar and hardware from the North exterior door. |
| 04/21/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove the slide bolt from the south entrance door. _____2. Remove the slide bolt from the North door by the office. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00783
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |