Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/20/2010

Applicant:

PARTNERS ON FOURTH INV LLC

Description:

Full Fire Prevention Inspection. Joe Harris 808-1443

Outstanding Inspections

Case Number: T10FR00771
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/20/2010 INSP - FULL JBURGE Correction Required Please correct all noted Tucson Fire Code violations.
04/20/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. All open spaces in the electrical panels located by the VIP door and liquor room shall be properly covered.
04/20/2010 VIOL - INT.FINISH, DEC. MATL'S JBURGE Correction Required IFC 807.1 General requirements. In occupancies in Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible. _____1. The curtains shall be fire-retardant. Provide the flame propagation performance criteria information it the curtrains have already been treated. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
04/20/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and test the automatic fire alarm system and provide the inspection report for Fire Department records.
04/20/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. Test all EXIT signs for internal illumination and emergency back-up power. Repair or replace any defective units.
04/20/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located in BAR 2. _____2. Repair or replace the broken emergency lighting unit located in the kitchen above the walk-in door.