Case: T10FR00771

Parcel: 11706078A


Addresses:

213 N 4TH AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00771

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/20/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. Test all EXIT signs for internal illumination and emergency back-up power. Repair or replace any defective units.
04/20/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the broken emergency lighting unit located in BAR 2.

_____2. Repair or replace the broken emergency lighting unit located in the kitchen above the walk-in door.