Case: T10FR00762
Case Details
Entered Date:
04/19/2010
Applicant:
MATIAS ALFONSO O & TERESA JT/RS
Description:
Full Fire Prevention Inspection. David Matias 624-4512
Outstanding Inspections
Case Number: T10FR00762
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Provide a copy of the kitchen hood extinguishing system inspection report for fire department records. |
| 04/19/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The EXIT sign located above the entrance door shall be illuminated. _____2. The EXIT sign located above the southeast exit door shall be illuminated. |
| 04/19/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located by the employee's restroom in the kitchen. _____2. Repair or replace the emergency lighting unit located by the dishwashing station in the kitchen. |
| 04/19/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove all locking devices from the southeast door that leads to the patio. Only Panic Hardware shall be allowed on the door. |
| 04/19/2010 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. The CO2 cylinders located behind the bar shall be properly secured with a chain or strap to prevent falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00762
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |