Case: T10FR00762

Parcel: 10321029Y

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00762

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/19/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. The EXIT sign located above the entrance door shall be illuminated.

_____2. The EXIT sign located above the southeast exit door shall be illuminated.
04/19/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed,
the panic or fire exit hardware shall be the only locking device on the door except
where otherwise permitted in this code.

_____1. Remove all locking devices from the southeast door that leads to the patio. Only Panic Hardware shall be allowed on the door.
04/19/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the emergency lighting unit located by the employee's restroom in the kitchen.

_____2. Repair or replace the emergency lighting unit located by the dishwashing station in the kitchen.