Case: T10FR00416
Case Details
Entered Date:
03/01/2010
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Sprinkler and alarm system inspection. Manuel 622-3000
Outstanding Inspections
Case Number: T10FR00416
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2010 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____1. Address numbers shall be in accordance with Pima County address display requirements. NOTE: Post the numbers on the sign located on Granada Ave. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
03/01/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised. IFC 903.4.1 Signals. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the fire code official, shall sound an audible signal at a constantly attended location. _____1. The sprinkler and fire alarm system shall be monitored and automatically transmit all trouble signals and sprinkler system water flow alarms. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00416
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson FIre Code violations have been corrected. |