Case: T10FR00416

Parcel: 11618432G


Addresses:

475 N GRANADA AV


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR00416

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/01/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 903.4 Sprinkler system monitoring and alarms. All valves
controlling the water supply for automatic sprinkler systems,
pumps, tanks, water levels and temperatures, critical air pressures,
andwater-flowswitches on all sprinkler systems shall be
electrically supervised.

IFC 903.4.1 Signals. Alarm, supervisory and trouble signals
shall be distinctly different and shall be automatically transmitted
to an approved central station, remote supervising
station or proprietary supervising station as defined in
NFPA 72 or, when approved by the fire code official, shall
sound an audible signal at a constantly attended location.

_____1. The sprinkler and fire alarm system shall be monitored and automatically transmit all trouble signals and sprinkler system water flow alarms.