Case: T10FR00369
Case Details
Entered Date:
02/17/2010
Applicant:
R J & J LLC
Description:
Full Fire Prevention Inspection. Jose Quiroz 245-2749
Outstanding Inspections
Case Number: T10FR00369
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord used to power the Bud Light neon sign. NOTE: Replace it with a fused power strip with a long cord. |
| 02/17/2010 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____1. Replace the missing ceiling tile located by the water heater. |
| 02/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service, tag and mount all portable fire extinguishers. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 02/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. _____1. Post the occupant load on a clearly visible sign on the wall by the main entrance. |
| 02/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove the slide bolt from the southwest EXIT door. _____2. Remove the slide bolts from the Northeast EXIT door. |
| 02/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception:Amain exit of a Group Aoccupancy in compliance with Section 1008.1.8.3, Item 2. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more then one-half the width of the door measured from the latch side. _____1. The Northeast EXIT double doors shall have panic hardware installed. |
| 02/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. IFC 1008.1 Doors. Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1017.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. IFC 1008.1.2 Door swing. Egress doors shall be side-hinged swinging.Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. _____1. Install an EXIT door equiped with panic hardware in the fenced area on the Northwest corner of the building, so occupants can exit from the outside fenced area. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00369
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |