Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

01/28/2010

Applicant:

CITY OF TUCSON

Description:

MAITS - FIRE CODE COMPLIANCE INSPECTION

Outstanding Inspections

Case Number: T10FR00236
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
01/28/2010 VIOL - BUILDING SVCS & SYSTEMS RHEATH Correction Required Emergency lighting units throughout the facility did not illuminate when tested. Repair units. INTERNATIONAL FIRE CODE 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.