Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T10FR00236
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2010 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Emergency lighting units throughout the facility did not illuminate when tested. Repair units. INTERNATIONAL FIRE CODE 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. |