Case: T10FR00236

Parcel: 12410004C


Addresses:

800 E 12TH ST


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR00236

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/28/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required Emergency lighting units throughout the facility did not illuminate when tested. Repair units. INTERNATIONAL FIRE CODE 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.