Case: T10FR00231
Case Details
Entered Date:
01/28/2010
Applicant:
CITY OF TUCSON
Description:
MAITS - FIRE CODE COMPLIANCE INSPECTION
Outstanding Inspections
Case Number: T10FR00231
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/28/2010 | VIOL - BUILDING SVCS & SYSTEMS | RHEATH | Correction Required | The emergency lighting unit did not operate when tested. Repair the lighting unit. INTERNATIONAL FIRE CODE (IFC) 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. |