Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T10FR00231
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2010 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | The emergency lighting unit did not operate when tested. Repair the lighting unit. INTERNATIONAL FIRE CODE (IFC) 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. |