Case: T10FR00083
Case Details
Entered Date:
01/14/2010
Applicant:
DRAGON S VIEW CORPORATION
Description:
Full Fire Prevention Inspection. Harry Gee 623-9855
Outstanding Inspections
Case Number: T10FR00083
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2010 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. Remove all storage from obstructing the sprinkler heads located in the dry storage room. |
01/14/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the Kitchen hood extinguishing system and repair any deficiencies noted on the inspection report. _____2. Provide the Automatic sprinkler system inspection report and correct any deficiencies noted on the report. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
01/14/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood system. NOTE: Provide documentation of the cleaning. |
01/14/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the kitchen EXIT door and replace it with a thumb-turn lock. |
01/14/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. Repair or replace the EXIT sign located in the entrance lobby. _____2. Repair or replace the EXIT sign located above the casheer station. _____3. Repair or replace the EXIT sign located above the northwest EXIT door in the dinning area. _____4. Repair or replace the EXIT sign located above the kitchen EXIT door. |
01/14/2010 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Properly secure the CO2 cylinders located by the dish washing station, to prevent falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00083
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |