Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T10FR00083

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/14/2010 VIOL - PRECAUTION AGAINST FIRE Correction Required IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

_____1. Remove all storage from obstructing the sprinkler heads located in the dry storage room.