Case: T10DV02786
Case Details
Entered Date:
05/04/2010
Applicant:
LIPLIL II LLC
Description:
#206 ----- TFD REQUESTING BUILDING SAFETY - FIRE SPRINKLERS WERE ACTIVATED ...NO FIRE
Outstanding Inspections
Case Number: T10DV02786
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2010 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | JVALDEZ | Item closed | |
06/07/2010 | NPO - INT. BUILDING MAINTENANC | JVALDEZ | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T10DV02786
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2010 | INSP - INITIAL CODE ENFORCMENT | JVALDEZ | Approved | EMERGENCY CALL OUT, SPRINKLER HEAD WAS DAMAGED IN BEDROOM WHICH CAUSED WATER DAMAGE TO THE CEILING, FLOORING AND EAST WALL OF THE UNIT WHICH HAS A SUBPANEL AND ONE RECEPTACLE. THE 6 CAR CARPORT, WHICH IS UNDER UNIT 206 HAS DAMAGE TO THE CEILINGS TYPE X DRYWALL THE AREA IS OF DAMAGE IS ESTIMATED AT 200 SQUARE FEET, PLUMBING COMPANY ON SITE AND MAINTENANCE PERSON STATED THAT THE CARPORT CEILING IS A SOFFIT FOR PLUMBING PIPES AND HAS NO ELECTRICAL CONDUCTORS, THERE ARE EXTERIOR LIGHTS UNDER THE CEILING AREA. TFD DID TURN POWER OFF AT THE SUB PANEL. I TURNED OFF POWER TO THE UNIT FROM THE MAIN DISCONNECT, MAINTENANCE TURNED POWER OFF TO THE EXTERIOR LIGHTS. NO TENANT WAS PRESENT. ORDER TO VACATE AND A NOTICE OF VIOLATION WAS ISSUED TO MANAGER KURT MINNO 520 237-0917. SPECIAL INSTRUCTIONS ON THE NOTICE OF VIOLATION WERE TO EVACUATE ALL WATER FROM THE INTERIOR OF THE UNIT WITHIN 10 DAYS. A ELECTRICIAN INSPECT AND SHALL PROVIDE A REPORT WHICH WILL STATES THE UNIT ELECTRICAL DEVICES ARE SAFE TO ENERGIZES, PRIOR TO ANYONE TURNING POWER BACK ON. THE NOTICE OF VIOLATION STATES THAT A PERMIT IS REQUIRED TO REPLACE THE TYPE X DRYWALL WITHIN 30 DAYS TO COMPLY, I ASKED THE MANAGER TO EXPOSED THE DAMAGE AREA AND CALL ME TO EVALUATE HOW MUCH DAMAGE WAS DONE AND TO AIR OUT THE WOOD MEMBERS. SCHEDULED FOLLOW UP INSPECTION 30 DAYS. |
06/07/2010 | INSP - FOLLOW UP CODE ENFORCE | JVALDEZ | Approved | PERMIT T10CM01429 FINAL 06/07/2010 REPAIR:DRYWALL NORTH SIDE CARPORT:T10DV02786 ALL REPAIRS COMPLETED UNDER PERMIT GRANTED OCCUPANCY CLOSE CASE |
Completed Activity Special Conditions
Case Description - EMERGENCY
Case Number - T10DV02786
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
Date | Name |
05/05/2010 | CONTACTED BY PHONE |
05/05/2010 | CONTACTED IN PERSON |
05/05/2010 | NOTICE AND ORDER ISSUED |
06/09/2010 | VIOLATION CLOSED |