Case: T09FR03911
Case Details
Entered Date:
12/30/2009
Applicant:
ALLUVIAL LLC
Description:
Full Fire Prevention Inspection. Daniel Cole 622-4300
Outstanding Inspections
Case Number: T09FR03911
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing light switch and electrical wiring covers located in the northeast storage room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 12/30/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. _____1. The northeast security grill shall swing outward in the direction of egress travel. |
| 12/30/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. _____1. The northwest patio door shall have panic hardware installed on the door. _____2. The patio gate shall have panic hardware installed on the inside of the gate. _____3. The northeast security grill shall have panic hardware installed on the inside of the security grill. ****NOTE: Panic hardware shall be the only locking device on the door. |
| 12/30/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the southeast door and replace it with a thumb-turn lock. |
| 12/30/2009 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Properly secure all compressed gas cylinders to prevent accidental falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03911
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2009 | INSP - FULL | JBURGE | Approved | Please correct all noted Tucson Fire Code violations. |