Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/30/2009

Applicant:

ALLUVIAL LLC

Description:

Full Fire Prevention Inspection. Daniel Cole 622-4300

Outstanding Inspections

Case Number: T09FR03911
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/30/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing light switch and electrical wiring covers located in the northeast storage room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
12/30/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. _____1. The northeast security grill shall swing outward in the direction of egress travel.
12/30/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. _____1. The northwest patio door shall have panic hardware installed on the door. _____2. The patio gate shall have panic hardware installed on the inside of the gate. _____3. The northeast security grill shall have panic hardware installed on the inside of the security grill. ****NOTE: Panic hardware shall be the only locking device on the door.
12/30/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the southeast door and replace it with a thumb-turn lock.
12/30/2009 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Properly secure all compressed gas cylinders to prevent accidental falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03911
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/30/2009 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.