Case: T09FR03906
Case Details
Entered Date:
12/29/2009
Applicant:
DUNPHY MICHAEL & JUDITHA CP/RS
Description:
insp
Outstanding Inspections
Case Number: T09FR03906
Case Status: PRECITE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2009 | INSP - FULL | EGriffin | Violation | On 12-29-09, a fire prevention inspection was conducted at Alfies 3940 East 29th Street, in Tucson Arizona. . The following Tucson Fire Code Violation(s) was noted: 1). Because of deep frying, Class K portable fire extinguisher is required. IFC904.11.5.2 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One Class K portable fire extinguisher of a minimum 1.5 gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One additional Class K portable fire extinguisher of a minimum 1.5 gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer's recommendations. This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 1-28-10 . A re-inspection shall be conducted at that time to ensure compliance. If you have questions, or if I may be of any assistance please call me at 791-4502 extension 127. |