Case: T09FR03905
Case Details
Entered Date:
12/29/2009
Applicant:
BROADWAY POWER CENTER GROUP LLC
Description:
Full inspection done 12/29/09; Josh Sticht - manager- 885-7200; "B" occupancy
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03905
Case Description: INSPECTION
Total Completed Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2009 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way. |
12/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. |
12/29/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. |
12/29/2009 | VIOL - PRECAUTION AGAINST FIRE | BCOBB | Approved | Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head. Thank you, |
12/29/2009 | INSP - FULL | BCOBB | Approved | Please correct the folowing: |