Case: T09FR03698
Case Details
Entered Date:
12/07/2009
Applicant:
PARK MU GIL & OAK MAI & PARK GEANIE Y & PARK
Description:
Inspection
Outstanding Inspections
Case Number: T09FR03698
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Blanks shall be installed to replace missing breakers in kitchen. |
| 12/07/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 609.1 Hood system shall be installed over grill in kitchen. |
| 12/07/2009 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Missing ceiling tile shall be replaced in kitchen. |
| 12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Extinguishers in event center shall be inspected. |
| 12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 K class extinguisher shall be inspected. |
| 12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Hood system shall be inspected at least every six months. |
| 12/07/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency lights in conference rooms. |
| 12/07/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency lights in event center. |
| 12/07/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 Exit signs in conference rooms. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03698
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2010 | INSP - FULL | TKNAPP | Approved |