Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/07/2009

Applicant:

DELTA BETA HOUSE LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03692
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
12/07/2009 VIOL - MEANS OF EGRESS JVINCENT Approved 1027.5 Illumination emergency power. ____Repair the following emergency lighting units. ____Back Exit. ____Next to kitchen double doors. ____Indoor stairwell.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ____I need to look in the kitchen. Make sure the hood system has had its 6month inspection and all deficiencies in report have been corrected. ____Make sure the hood system/filters are clean.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Extinguishers need to be serviced and tagged. ____Replace any extinguishers missing from cabinets.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Test every smoke detector and record in log. Provide log during reinspection.
12/07/2009 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION.