Case: T09FR03692

Parcel: 117033520


Addresses:

638 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR03692

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

____Test every smoke detector and record in log. Provide log during reinspection.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Extinguishers need to be serviced and tagged.
____Replace any extinguishers missing from cabinets.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.1 General. Automatic fire-extinguishing systems, other
than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions
of this section and the applicable referenced standards.

____I need to look in the kitchen. Make sure the hood system has had its 6month inspection and all deficiencies in report have been corrected.
____Make sure the hood system/filters are clean.