Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR03692
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Test every smoke detector and record in log. Provide log during reinspection. |
|
12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Extinguishers need to be serviced and tagged. ____Replace any extinguishers missing from cabinets. |
|
12/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ____I need to look in the kitchen. Make sure the hood system has had its 6month inspection and all deficiencies in report have been corrected. ____Make sure the hood system/filters are clean. |