FIELD

Type:

INSPECTION

Entered Date:

12/03/2009

Applicant:

CITY OF TUCSON

Description:

FIRE SPRINKLER SYSTEM INSPECTION

Outstanding Inspections

Case Number: T09FR03688
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/03/2009 VIOL - FIRE PROTECTION SYSTEMS RHEATH Correction Required Bldg D Entryway to room D-1: There is an 18" x 9' x 4' high unsprinklered area above the door. Install additional sprinkler protection for this area. The 2002 edition of NFPA 13, 8.6.7. Ceiling Pockets. Contact Harvey Brown or Carl Schultz for specific requirements, exceptions, or alternatives.