Case: T09FR03688
Case Details
Entered Date:
12/03/2009
Applicant:
CITY OF TUCSON
Description:
FIRE SPRINKLER SYSTEM INSPECTION
Outstanding Inspections
Case Number: T09FR03688
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Correction Required | Bldg D Entryway to room D-1: There is an 18" x 9' x 4' high unsprinklered area above the door. Install additional sprinkler protection for this area. The 2002 edition of NFPA 13, 8.6.7. Ceiling Pockets. Contact Harvey Brown or Carl Schultz for specific requirements, exceptions, or alternatives. |