Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Bldg D Entryway to room D-1: There is an 18" x 9' x 4' high unsprinklered area above the door. Install additional sprinkler protection for this area. The 2002 edition of NFPA 13, 8.6.7. Ceiling Pockets. Contact Harvey Brown or Carl Schultz for specific requirements, exceptions, or alternatives. |