Case: T09FR03688

Parcel: 11522002A


Addresses:

1390 W SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR03688

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/03/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required Bldg D Entryway to room D-1: There is an 18" x 9' x 4' high unsprinklered area above the door. Install additional sprinkler protection for this area. The 2002 edition of NFPA 13, 8.6.7. Ceiling Pockets.

Contact Harvey Brown or Carl Schultz for specific requirements, exceptions, or alternatives.