Case: T09FR03684
Case Details
Entered Date:
12/03/2009
Applicant:
MARLEE SPEEDWAY CHUY S LLC
Description:
Full Fire Prevention Inspection. Mitch Taylor 326-4969
Outstanding Inspections
Case Number: T09FR03684
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located on the wall by the "TEKKEN 2" game. |
| 12/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the kitchen hood extinguishing system and correct any deficiencies noted on the inspection report. _____2. Align the hood extinguishing system nozzles to properly cover the cooking equipment. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 12/03/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The East EXIT sign shall be internally illuminated. _____2.The West EXIT sign shall be internally illuminated. _____3. The EXIT sign located in the kitchen shall be interternally illuminated. |
| 12/03/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located in the Men's restroom. _____2. Repair or replace the broken emergency lighting unit located in the Women's restroom. _____3. Repair or replace the broken emergency lighting unit located above the arcade games. _____4. Repair or replace the broken emergency lighting unit located above the West entrance door. _____5. Repair or replace the broken emergency lighting unit located above the East entrance door by the "TUNA". |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03684
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | INSP - FULL | JBURGE | Approved | Please correct all noted Tucson Fire Code violations. |