Case: T09FR03684

Parcel: 12510052A


Addresses:

3100 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03684

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/03/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. The East EXIT sign shall be internally illuminated.

_____2.The West EXIT sign shall be internally illuminated.

_____3. The EXIT sign located in the kitchen shall be interternally illuminated.
12/03/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the broken emergency lighting unit located in the Men's restroom.

_____2. Repair or replace the broken emergency lighting unit located in the Women's restroom.

_____3. Repair or replace the broken emergency lighting unit located above the arcade games.

_____4. Repair or replace the broken emergency lighting unit located above the West entrance door.

_____5. Repair or replace the broken emergency lighting unit located above the East entrance door by the "TUNA".