Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

12/03/2009

Applicant:

CITY OF TUCSON

Description:

FIRE SPRINKLER SYSTEM INSPECTION

Outstanding Inspections

Case Number: T09FR03681
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/03/2009 VIOL - FIRE PROTECTION SYSTEMS RHEATH Correction Required The covered patios do not have sprinkler protection. Install sprinklers to provide full covereage. IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.