Case: T09FR03681

Parcel: 133110010

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR03681

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/03/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required The covered patios do not have sprinkler protection. Install sprinklers to provide full covereage. IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.