Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/01/2009

Applicant:

JAGOR

Description:

FULL FIRE INSPECTION. CONTACT-NOBORU NAKAJIMA

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03669
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
12/01/2009 VIOL - COMPRESSED GASES WMOTTO Approved IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ___1. SECURE BOTTLES IN KITCHEN PROPERLY TO WALL TO PREVENT BOTTLES FROM FALLING.
12/01/2009 VIOL - MEANS OF EGRESS WMOTTO Approved IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. ____1. REPAIR EXIT SIGN BY MENS BATHROOM. Re-inspection date scheduled on or after November 12th, 2009. If you have any questions or concerns please call Inspector Mtto at 837-7106. Thank you, _____________________________________________ William Motto, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________
12/01/2009 VIOL - MEANS OF EGRESS WMOTTO Approved IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____1. REMOVE SLIDE LOCK ON REAR EXIT IN KITCHEN. ____2. LOCK NEEDS TO BE REMOVED BY MENS BATHROOM REAR EXIT.
12/01/2009 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Approved IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ___1. HOOD SYSTEM IN KITCHEN SHALL BE SERVICED AND REPAIR ANY DEFICIENCIES NOTED ON THE REPORT. ___2. NOZZLES ON HOOD SYSTEMS NEED TO BE ADJUSTED FOR PROPER COVERAGE.
12/01/2009 VIOL - BUILDING SVCS & SYSTEMS WMOTTO Approved IFC 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. ____1. NEED TO HAVE ELECTRICAL CORDS BEHIND SUSHI BAR PLUGGED INTO AN APPROVED POWER STRIP. ____2. FRIDGE IN KITCHEN NEEDS TO BE PLUGGED INTO OUTLET OR AN APPROVED POWER STRIP.
12/01/2009 INSP - FULL WMOTTO Approved PLEASE CORRECT ALL NOTED TUCSON FIRE CODE VIOLATIONS.