Case: T09FR03669

Parcel: 11309224A


Addresses:

857 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03669

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
02/03/2010 VIOL - MEANS OF EGRESS Approved ALL VIOLATIONS CORRECTED UPON REINSPECTION
12/01/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

____1. REMOVE SLIDE LOCK ON REAR EXIT IN KITCHEN.
____2. LOCK NEEDS TO BE REMOVED BY MENS BATHROOM REAR EXIT.
12/01/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator.

____1. REPAIR EXIT SIGN BY MENS BATHROOM.

Re-inspection date scheduled on or after November 12th, 2009.
If you have any questions or concerns please call Inspector Mtto at 837-7106.
Thank you,

_____________________________________________
William Motto, Inspector, Tucson Fire Department


__________________________ - I have received a copy of this inspection report.
Building Representative


Re-inspection approved: ___________________________Date:__________


Captain - Tucson Fire Dept. ________________________________________