Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR03669
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2010 | VIOL - MEANS OF EGRESS | Approved | ALL VIOLATIONS CORRECTED UPON REINSPECTION | |
12/01/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____1. REMOVE SLIDE LOCK ON REAR EXIT IN KITCHEN. ____2. LOCK NEEDS TO BE REMOVED BY MENS BATHROOM REAR EXIT. |
|
12/01/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. ____1. REPAIR EXIT SIGN BY MENS BATHROOM. Re-inspection date scheduled on or after November 12th, 2009. If you have any questions or concerns please call Inspector Mtto at 837-7106. Thank you, _____________________________________________ William Motto, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________ |