Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/18/2009

Applicant:

ST JOSEPHS HOSPITAL OF TUCSON

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03606
Case Description: INSPECTION
Total Completed Inspections - 21
End Date Description Inspector Results Comments
11/18/2009 INSP - FULL RSPANGLE Approved 21.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET #250-06A ON 2ND FLOOR OF O'REILLY CENTER.
11/18/2009 INSP - FULL RSPANGLE Approved 20.) TFC 703.1.1 REPLACE CEILING TILE ON 3RD FLOOR AMBULATORY SURGERY AREA BY BED 19.
11/18/2009 INSP - FULL RSPANGLE Approved 19.) TFC 605.5 REMOVE EXTENSION CORD BEING USED IN BALANCE CENTER EXAM ROOM.
11/18/2009 INSP - FULL RSPANGLE Approved 18.) TFC 605.5 REMOVE EXTENSION CORD IN USE IN OCCUPATIONAL HEALTH OFFICE. # 160-040B.
11/18/2009 INSP - FULL RSPANGLE Approved 17.) TFC 901.6 REPLACE MISSING SPINKLER HEAD ESCUTCHEON IN EMERGENCY PATIENT WAITING AREA 1ST FLOOR.
11/18/2009 INSP - FULL RSPANGLE Approved 16.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR EAST HALL STAFF ROOM.
11/18/2009 INSP - FULL RSPANGLE Approved 15.) TFC 605.5 REMOVE EXTENSION CORD FROM USE IN EVS SUPPLY ROOM IN BASEMENT.
11/18/2009 INSP - FULL RSPANGLE Approved 14.) TFC 703.1.1 SEAL AROUND CONDUIT IN SPD WATER TREATMENT ROOM.
11/18/2009 INSP - FULL RSPANGLE Approved 13.) TFC 703.1.1 SEAL AROUND CABLE AND CONDUIT IN BASEMENT SECURITY ROOM.
11/18/2009 INSP - FULL RSPANGLE Approved 12.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM.
11/18/2009 INSP - FULL RSPANGLE Approved 11.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN SOUTH EAST CORNER OF WOODSHOP.
11/18/2009 INSP - FULL RSPANGLE Approved 10.) TFC 703.1.1 SEAL ELECTRICAL CONDUIT IN ELECTRICAL VAULT IN BASEMENT.
11/18/2009 INSP - FULL RSPANGLE Approved 9.) TFC 315.2.1 REMOVE STORAGE FROM TOP SHELF IN BATTERY STORAGE ROOM WEST WALL IN BASEMENT.
11/18/2009 INSP - FULL RSPANGLE Approved 8.) TFC 1011.4 EXIT SIGN IN BASEMENT BY DIETICIAN'S OFFICE MUST BE ILLUMINATED.
11/18/2009 INSP - FULL RSPANGLE Approved 7.) TFC 904.11.7 AN 8" SHEETMETAL BAFFLE IS REQUIRED BETWEEN DEEP FRYER AND GRILL IN CAFETERIA.
11/18/2009 INSP - FULL RSPANGLE Approved 6.) TFC 605.6 OPEN WIRE SPLICES IN LIGHTING FIXTURE IN BASEMENT RECORDS AREA NORTH WALL MUST HAVE A COVER PLATE INSTALLED.
11/18/2009 INSP - FULL RSPANGLE Approved 5.) TFC 3003.5.3 COMPRESSED GAS CYLINDERS IN BASEMENT MECHANICAL ROOM B-1 MUST BE SECURED TO PREVENT FALLING.
11/18/2009 INSP - FULL RSPANGLE Approved 4.) TFC 315.2.1 STORAGE MUST BE KEPT 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM B-10.
11/18/2009 INSP - FULL RSPANGLE Approved 3.) TFC 901.6 REPLACE SPRINKLER HEAD PROTECTIVE CAGE IN BASEMENT MECHANICAL ROOM B-10.
11/18/2009 INSP - FULL RSPANGLE Approved 2.) TFC 901.6 REMOVE PLASTIC COVERING FROM SMOKE DETECTOR IN MECHANICAL ROOM B-4.
11/18/2009 INSP - FULL RSPANGLE Approved 1.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON CEILING BY SERVICE ELEVATOR IN BASEMENT.