Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T09FR03606

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/25/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
NOTE: F/A ANNUAL INSP REPORT WAS SUBMITTED. KAZAL WILL FORWARD COPY OF S/S ANNUAL.
11/18/2009 INSP - FULL Violation 1.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON CEILING BY SERVICE ELEVATOR IN BASEMENT.
11/18/2009 INSP - FULL Violation 2.) TFC 901.6 REMOVE PLASTIC COVERING FROM SMOKE DETECTOR IN MECHANICAL ROOM B-4.
11/18/2009 INSP - FULL Violation 3.) TFC 901.6 REPLACE SPRINKLER HEAD PROTECTIVE CAGE IN BASEMENT MECHANICAL ROOM B-10.
11/18/2009 INSP - FULL Violation 4.) TFC 315.2.1 STORAGE MUST BE KEPT 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM B-10.
11/18/2009 INSP - FULL Violation 5.) TFC 3003.5.3 COMPRESSED GAS CYLINDERS IN BASEMENT MECHANICAL ROOM B-1 MUST BE SECURED TO PREVENT FALLING.
11/18/2009 INSP - FULL Violation 6.) TFC 605.6 OPEN WIRE SPLICES IN LIGHTING FIXTURE IN BASEMENT RECORDS AREA NORTH WALL MUST HAVE A COVER PLATE INSTALLED.
11/18/2009 INSP - FULL Violation 7.) TFC 904.11.7 AN 8" SHEETMETAL BAFFLE IS REQUIRED BETWEEN DEEP FRYER AND GRILL IN CAFETERIA.
11/18/2009 INSP - FULL Violation 8.) TFC 1011.4 EXIT SIGN IN BASEMENT BY DIETICIAN'S OFFICE MUST BE ILLUMINATED.
11/18/2009 INSP - FULL Violation 9.) TFC 315.2.1 REMOVE STORAGE FROM TOP SHELF IN BATTERY STORAGE ROOM WEST WALL IN BASEMENT.
11/18/2009 INSP - FULL Violation 10.) TFC 703.1.1 SEAL ELECTRICAL CONDUIT IN ELECTRICAL VAULT IN BASEMENT.
11/18/2009 INSP - FULL Violation 11.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN SOUTH EAST CORNER OF WOODSHOP.
11/18/2009 INSP - FULL Violation 12.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM.
11/18/2009 INSP - FULL Violation 13.) TFC 703.1.1 SEAL AROUND CABLE AND CONDUIT IN BASEMENT SECURITY ROOM.
11/18/2009 INSP - FULL Violation 14.) TFC 703.1.1 SEAL AROUND CONDUIT IN SPD WATER TREATMENT ROOM.
11/18/2009 INSP - FULL Violation 15.) TFC 605.5 REMOVE EXTENSION CORD FROM USE IN EVS SUPPLY ROOM IN BASEMENT.
11/18/2009 INSP - FULL Violation 16.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR EAST HALL STAFF ROOM.
11/18/2009 INSP - FULL Violation 17.) TFC 901.6 REPLACE MISSING SPINKLER HEAD ESCUTCHEON IN EMERGENCY PATIENT WAITING AREA 1ST FLOOR.
11/18/2009 INSP - FULL Violation 18.) TFC 605.5 REMOVE EXTENSION CORD IN USE IN OCCUPATIONAL HEALTH OFFICE. # 160-040B.
11/18/2009 INSP - FULL Violation 19.) TFC 605.5 REMOVE EXTENSION CORD BEING USED IN BALANCE CENTER EXAM ROOM.
11/18/2009 INSP - FULL Violation 20.) TFC 703.1.1 REPLACE CEILING TILE ON 3RD FLOOR AMBULATORY SURGERY AREA BY BED 19.
11/18/2009 INSP - FULL Violation 21.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET #250-06A ON 2ND FLOOR OF O'REILLY CENTER.