Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR03606
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. NOTE: F/A ANNUAL INSP REPORT WAS SUBMITTED. KAZAL WILL FORWARD COPY OF S/S ANNUAL. |
|
11/18/2009 | INSP - FULL | Violation | 1.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON CEILING BY SERVICE ELEVATOR IN BASEMENT. | |
11/18/2009 | INSP - FULL | Violation | 2.) TFC 901.6 REMOVE PLASTIC COVERING FROM SMOKE DETECTOR IN MECHANICAL ROOM B-4. | |
11/18/2009 | INSP - FULL | Violation | 3.) TFC 901.6 REPLACE SPRINKLER HEAD PROTECTIVE CAGE IN BASEMENT MECHANICAL ROOM B-10. | |
11/18/2009 | INSP - FULL | Violation | 4.) TFC 315.2.1 STORAGE MUST BE KEPT 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM B-10. | |
11/18/2009 | INSP - FULL | Violation | 5.) TFC 3003.5.3 COMPRESSED GAS CYLINDERS IN BASEMENT MECHANICAL ROOM B-1 MUST BE SECURED TO PREVENT FALLING. | |
11/18/2009 | INSP - FULL | Violation | 6.) TFC 605.6 OPEN WIRE SPLICES IN LIGHTING FIXTURE IN BASEMENT RECORDS AREA NORTH WALL MUST HAVE A COVER PLATE INSTALLED. | |
11/18/2009 | INSP - FULL | Violation | 7.) TFC 904.11.7 AN 8" SHEETMETAL BAFFLE IS REQUIRED BETWEEN DEEP FRYER AND GRILL IN CAFETERIA. | |
11/18/2009 | INSP - FULL | Violation | 8.) TFC 1011.4 EXIT SIGN IN BASEMENT BY DIETICIAN'S OFFICE MUST BE ILLUMINATED. | |
11/18/2009 | INSP - FULL | Violation | 9.) TFC 315.2.1 REMOVE STORAGE FROM TOP SHELF IN BATTERY STORAGE ROOM WEST WALL IN BASEMENT. | |
11/18/2009 | INSP - FULL | Violation | 10.) TFC 703.1.1 SEAL ELECTRICAL CONDUIT IN ELECTRICAL VAULT IN BASEMENT. | |
11/18/2009 | INSP - FULL | Violation | 11.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN SOUTH EAST CORNER OF WOODSHOP. | |
11/18/2009 | INSP - FULL | Violation | 12.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN BASEMENT MECHANICAL ROOM. | |
11/18/2009 | INSP - FULL | Violation | 13.) TFC 703.1.1 SEAL AROUND CABLE AND CONDUIT IN BASEMENT SECURITY ROOM. | |
11/18/2009 | INSP - FULL | Violation | 14.) TFC 703.1.1 SEAL AROUND CONDUIT IN SPD WATER TREATMENT ROOM. | |
11/18/2009 | INSP - FULL | Violation | 15.) TFC 605.5 REMOVE EXTENSION CORD FROM USE IN EVS SUPPLY ROOM IN BASEMENT. | |
11/18/2009 | INSP - FULL | Violation | 16.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR EAST HALL STAFF ROOM. | |
11/18/2009 | INSP - FULL | Violation | 17.) TFC 901.6 REPLACE MISSING SPINKLER HEAD ESCUTCHEON IN EMERGENCY PATIENT WAITING AREA 1ST FLOOR. | |
11/18/2009 | INSP - FULL | Violation | 18.) TFC 605.5 REMOVE EXTENSION CORD IN USE IN OCCUPATIONAL HEALTH OFFICE. # 160-040B. | |
11/18/2009 | INSP - FULL | Violation | 19.) TFC 605.5 REMOVE EXTENSION CORD BEING USED IN BALANCE CENTER EXAM ROOM. | |
11/18/2009 | INSP - FULL | Violation | 20.) TFC 703.1.1 REPLACE CEILING TILE ON 3RD FLOOR AMBULATORY SURGERY AREA BY BED 19. | |
11/18/2009 | INSP - FULL | Violation | 21.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET #250-06A ON 2ND FLOOR OF O'REILLY CENTER. |