Case: T09FR03454
Case Details
Entered Date:
11/04/2009
Applicant:
GAMMA DELTA HOLDING CORP
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03454
Case Description: INSPECTION
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised OR LOCKED IN THE OPEN POSITION. ____Lock the control valve in the open position. Currently has a chain around the valve but no lock. |
| 11/04/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1027.5 Illumination emergency power. ____Repair the emergency lighting unit in the chapter room. |
| 11/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Complete smoke detector log and provide upon reinspection. Every bedroom, bedroom hallways and any rooms used for sleeping purposes requires a smoke detector. ____Fire alarm due for annual inspection and repair. It is currently showing a trouble code. ____Provide a copy of the annual sprinkler inspection report. Make sure all the deficiencies noted are repaired. |
| 11/04/2009 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Approved | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____Install "blank" in electrical panel located near laundry room. |
| 11/04/2009 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Approved | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Trim vegetation around Fire Dept Connections. |
| 11/04/2009 | INSP - FULL | JVINCENT | Approved | FULL FIRE INSPECTION. |