Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/04/2009

Applicant:

GAMMA DELTA HOLDING CORP

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03454
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised OR LOCKED IN THE OPEN POSITION. ____Lock the control valve in the open position. Currently has a chain around the valve but no lock.
11/04/2009 VIOL - MEANS OF EGRESS JVINCENT Approved 1027.5 Illumination emergency power. ____Repair the emergency lighting unit in the chapter room.
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Complete smoke detector log and provide upon reinspection. Every bedroom, bedroom hallways and any rooms used for sleeping purposes requires a smoke detector. ____Fire alarm due for annual inspection and repair. It is currently showing a trouble code. ____Provide a copy of the annual sprinkler inspection report. Make sure all the deficiencies noted are repaired.
11/04/2009 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Approved 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____Install "blank" in electrical panel located near laundry room.
11/04/2009 VIOL - FIRE SERVICE FEATURES JVINCENT Approved 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Trim vegetation around Fire Dept Connections.
11/04/2009 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION.