Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR03454
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 11/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Complete smoke detector log and provide upon reinspection. Every bedroom, bedroom hallways and any rooms used for sleeping purposes requires a smoke detector. ____Fire alarm due for annual inspection and repair. It is currently showing a trouble code. ____Provide a copy of the annual sprinkler inspection report. Make sure all the deficiencies noted are repaired. |
|
| 11/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised OR LOCKED IN THE OPEN POSITION. ____Lock the control valve in the open position. Currently has a chain around the valve but no lock. |