Case: T09FR03454

Parcel: 12317201E


Addresses:

1525 E DRACHMAN ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR03454

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Complete smoke detector log and provide upon reinspection. Every bedroom, bedroom hallways and any rooms used for sleeping purposes requires a smoke detector.
____Fire alarm due for annual inspection and repair. It is currently showing a trouble code.
____Provide a copy of the annual sprinkler inspection report. Make sure all the deficiencies noted are repaired.
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 903.4 Sprinkler system monitoring and alarms. All valves
controlling the water supply for automatic sprinkler systems,
pumps, tanks, water levels and temperatures, critical air pressures,
andwater-flowswitches on all sprinkler systems shall be
electrically supervised OR LOCKED IN THE OPEN POSITION.

____Lock the control valve in the open position. Currently has a chain around the valve but no lock.