Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR03311
Case Details
Entered Date:
10/20/2009
Applicant:
SAINT JOHN THE EVANGELIST ROMAN
Description:
FIRE CODE COMPLIANCE INSPECTION
Outstanding Inspections
Case Number: T09FR03311
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2009 | INSP - FULL | RHEATH | Correction Required | A Fire Code Compliance Inspection was conducted noting the following discrepancies. A 11/10/2009 suspense has been established for full compliance. R. HEATH, INSPECTOR _______________________ M. JONES, CAPTAIN _______________________ |
10/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | RHEATH | Correction Required | 1. Classroom # 11. 3 power strips connected in series. Discontinue this practice. IFC 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. 2. Classroom # 13: Covers are broken / missing on 6 - 2 prong electrical outlets. Replace covers. IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
10/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Correction Required | 1. Kitchen: there is no record of the hood and duct system being cleaned over the commercial cooking equipment. Have system cleaned. NFPA 96, 11.3: Table 11.3. Systems serving low volume cooking operations shall be cleaned annually. |