Case: T09FR03311

Parcel: 11918036A


Addresses:

600 W AJO WY


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR03311

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/20/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 1. Classroom # 11. 3 power strips connected in series. Discontinue this practice. IFC 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
2. Classroom # 13: Covers are broken / missing on 6 - 2 prong electrical outlets. Replace covers. IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.