Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/19/2009

Applicant:

CARS-DB2 LLC

Description:

Permit to secure area without additional sprinkler - O'Riley Chevrolet/Corvette Cafe

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03292
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/19/2009 INSP - LIFE SAFETY DGREENLE Approved This letter shall serve as a permit (T09FR03292) to secure the 4'9" x 3'6" area in the employee break area in O'Riley Chevrolet/Corvette Café, 6100 E. Broadway Bl. The requirements for construction of a secure area are as follows. Storage must be maintained a minimum 18" below ceiling. This does not apply to storage against wall. Against-wall storage may not project more than 12" into room (or it must be 18" down). Clearance around and below sprinkler heads must be 18" whether against wall of not. No area may be enclosed without adding sprinklers. The area may be secured by fencing/caging material. Fencing/caging material must be 75% open to allow sprinkler coverage. Framing may not excessively disrupt spray pattern.