Inspection History Details
Inspection Status: Approved
Inspection History: INSP - LIFE SAFETY
Case Number - T09FR03292
Inspection Description - INSP - LIFE SAFETY
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2009 | INSP - LIFE SAFETY | Approved | This letter shall serve as a permit (T09FR03292) to secure the 4'9" x 3'6" area in the employee break area in O'Riley Chevrolet/Corvette Café, 6100 E. Broadway Bl. The requirements for construction of a secure area are as follows. Storage must be maintained a minimum 18" below ceiling. This does not apply to storage against wall. Against-wall storage may not project more than 12" into room (or it must be 18" down). Clearance around and below sprinkler heads must be 18" whether against wall of not. No area may be enclosed without adding sprinklers. The area may be secured by fencing/caging material. Fencing/caging material must be 75% open to allow sprinkler coverage. Framing may not excessively disrupt spray pattern. |